Why Do Windows and Balcony Doors Leak Even After Resealing?
Owners, builders, agents and building professionals
A window or balcony door can still leak after resealing because water can pass through the unit, behind its perimeter or down the wall from an opening higher up. A new bead closes only the joint it actually spans. It cannot reconnect a flashing to the wall's concealed drainage layer or fix a balcony membrane that terminates below the water it is supposed to stop. Find the route before choosing which detail to repair.
For an assessment of recurring leaks or other building defects, explore our building defects inspections. An article cannot determine the cause or appropriate solution for an individual property.
The first wet spot and the entry point may differ
Water appearing at an interior sill, jamb or threshold just tells you where it became visible. Look at its position relative to other openings and the wall above, and whether it appears during wind-driven rain, water on the balcony or other conditions. A wet head above a door directs attention to the installation around and above that door as well as to the door itself. A stain left after drying may preserve the exit point rather than the path.
Check what changed when the unit was installed or replaced. A frame can be neatly sealed to trim that was never connected to the drainage layer behind the cladding. Later decking or tiling can change the external level in relation to the threshold without any change to the door frame. Those are different faults and need different enquiries.
What pan, jamb and head flashings do
An opening interrupts the drainage plane behind the cladding. Head flashing intercepts water descending from above; sill or pan flashing manages water reaching the lower part of the opening. The laps at the jambs and corners have to connect those details to the adjacent water-resistive layer so that water is shed to the outside rather than behind the next layer. A piece of metal visible at the head says nothing about whether water from above lands in front of it.
The lower corners are particularly vulnerable in a framed opening because wrapping and joining the drainage layer there is difficult. The pan needs a path out; protection that collects water but discharges it into the wall does not do its job. Follow the particular frame and wall assembly instead of copying a generic pan detail from another product.
Where the balcony membrane meets the sill
For doors and windows onto external waterproofed areas, AS 4654.2-2012 clause 2.8.3 requires sub-sill flashing as part of the membrane system. For the Class 2, 3 and 9c context addressed here, check whether this is part of the applicable NCC 2022 Volume One Deemed-to-Satisfy pathway. Do not carry the same detail across to a different building class or separately approved system without checking the design basis.
Under AS 4654.2-2012 clause 2.8.1.1, where an upturn prevents entry its height above the outside finished surface must be enough to prevent overtopping, including by wind-driven water. Seeing the top of a strip does not show how it joins the sub-sill. A raised finish can reduce the effective height without tearing the membrane.
If the inside and outside finished levels do not allow an upturn, AS 4654.2-2012 clause 2.8.3 calls for the membrane to be fixed under the sill and terminate in the stormwater system. That is an alternative drainage path, not permission to omit the upturn without providing one. Check the exterior finish level, outlet and membrane connection separately.
The patio door fed by a higher window
In one documented case, wetting immediately above the patio door did not reproduce the leak. Testing the window above brought droplets to the door head. Behind the cladding, a gap in the foam sheathing let water from the window travel past the door flashing instead of being shed outside.
That case depended on the combination of localised testing and seeing the concealed detail. Droplets at the door head alone would not distinguish it from a problem with the head seal. The earlier sealant on the upper window trim was an observation, not proof of the route until the investigation reproduced it.
What changes when trim goes in first
In a separate documented case, the trim went in before the water-resistive layer and manufactured stone veneer. The wrap stopped at the trim and flashing was missing at that junction. Staining below corners and centre mullions pointed to the need to check the assembly sequence rather than just apply sealant over the visible joints.
A pre-cover photograph of the identified opening may distinguish a flashing hidden behind trim from a flashing that was never installed. A detail on a drawing shows the intended continuity; it cannot substitute for a view of that connection as built.
Which part would the repair actually change?
A fault within a glazed unit is different from a fault in the surrounding wall. Flashings can limit entry at an opening, restrict transfer across a cavity or direct water out through the cladding. Fixing a frame joint does not reconnect a break in the wall's drainage path.
Price and assess the work against the verified route: the unit itself, the wall connection, the balcony threshold, or more than one of these.
What a targeted water test can establish
Wetting everything at once may reproduce the symptom without isolating a path. The investigator should choose the next area to test from the observations, note what responds, and consider whether the test represented the conditions under which the leak normally appears.
Specify the supported route and any material uncertainty before choosing between a frame repair and work behind the surround. Let the investigator decide whether testing or authorised opening-up is needed to distinguish them.